A residual current device (RCD) cuts the power when current takes a different path from the one it should, for example through a faulty appliance or through a person. On its page about the RCD, the Swedish National Electrical Safety Board, Elsäkerhetsverket, calls it “a cheap life insurance that also protects against electrical fires”. It is required in new homes, but not retrospectively in older houses.
How it works
In a fault-free circuit, as much current flows out in the phase conductor as comes back in the neutral conductor. The RCD compares the two. If part of the current leaks to earth there is a difference, and when the difference reaches the device’s rated value it switches off.
An RCD for personal protection must be marked 30 mA, which may also be written as 0.03 A. That is a very small current compared with what a fuse lets through, and that is the whole point. Elsäkerhetsverket writes: “The RCD – not the fuse – senses, in the event of a fault, the small currents to earth that can cause a fire.”
| Property | Fuse | RCD |
|---|---|---|
| Reacts to | Too high a current: overload or short circuit | Current that leaks to earth |
| Mainly protects | The cables from getting too hot | People from current through the body, and the house from fire |
| Marked with | For example 10 A or 16 A | 30 mA for personal protection |
| Usually trips when | Too many appliances are running on the same circuit | An appliance or cable has an insulation fault, or moisture has got in |
So the two do not replace each other. According to Elsäkerhetsverket, the RCD is protection that supplements fuses and protective earthing. It also protects unearthed sockets, but it does not replace earthing.
When the requirement came
| Date | What began to apply |
|---|---|
| 1 May 1996 | RCD for sockets up to 16 A outdoors |
| 1 January 2000 | RCD in newly built homes, and in compulsory schools, preschools and after-school centres |
| 1 December 2022 | The explicit requirement was removed from Elsäkerhetsverket’s regulations. The requirement is in the Swedish standard instead |
About the rules from 1996 and 2000, Elsäkerhetsverket writes that they applied to the construction of installations, alterations and extensions: “They were not retroactive in existing installations.”
The change in 2022 does not mean that the requirement disappeared. The regulation points to the Swedish standard as the way to meet the requirement for good electrical safety practice, and an electrical installation company (elinstallationsföretag) that chooses not to follow the standard must be able to show that safety is just as high anyway.
Where it is required today
Elsäkerhetsverket sums up the position like this: “Today’s electrical regulations require an RCD as additional protection for practically all sockets.” It is a requirement in all newly built homes.
| Situation | Is an RCD required? |
|---|---|
| Newly built home | Yes |
| New socket outdoors | Yes |
| New or rebuilt bathroom | Yes, on all circuits that supply the bathroom |
| New underfloor heating | Yes, according to the standard |
| EV charger (wallbox) | Yes, one of its own. It may not be connected downstream of the house’s existing RCD |
| Older house where nothing is being altered | No, but it is recommended |
| Straight replacement of the consumer unit | No, but it is recommended |
| Replacement of a broken socket | No, but it is recommended |
If you are adding to an older house, there is one exception. When the installation is extended with new sockets within an existing dry room, the RCD requirement does not apply if the home’s installation was built before 1 January 2000. Elsäkerhetsverket nevertheless always recommends adding one.
Older houses without an RCD
You do not have to fit an RCD just because the house is old. Elsäkerhetsverket’s advice is clear all the same: if you do not have one, you should have an electrical installation company install one, and an old installation is an extra reason.
A few things decide how it is done:
- Who may do it. RCDs in the fixed installation must be fitted by a registered electrical installation company. It is not something you may do yourself.
- One or several. A single RCD for the whole house gives protection, but when it trips everything loses power, the freezer included. With several RCDs only part of the house goes dark, and the fault is easier to find.
- Type. For general-purpose sockets Elsäkerhetsverket recommends type A, and that older devices of type AC are replaced.
- Age. If your RCD was made before 1996, Elsäkerhetsverket recommends that you replace it. That year tests were introduced that show the device can cope with different environments. There is no best-before date, but RCDs do not last for ever.
- Portable RCDs. You may plug in a portable RCD yourself. It is one way to increase safety at older outdoor sockets.
Test it twice a year
It is the holder of the installation (innehavare), the owner or user who is responsible for it, who has to make sure the RCD works. The test takes half a minute.
- Find the RCD in the consumer unit. It has a test button, often marked T or Test.
- Press the button. The power should be cut immediately in the part of the house that the RCD protects.
- Switch the RCD back on.
- If the power is not cut, contact an electrical installation company straight away.
Elsäkerhetsverket has no requirement on intervals but recommends at least twice a year. Some manufacturers state once a month, so read the instructions for your device. A simple way to remember is to test when you change the clocks.
If the RCD trips without your having pressed the button, it has found a fault. How to narrow it down is described in the article on when the RCD trips.
What it costs
The price list has two versions of the same RCD, without and with an enclosure of its own, and a smaller device for underfloor heating. The smaller one is an RCBO, that is, an RCD and a circuit breaker in one unit. Circuit breakers are fuses that switch off and can be switched on again.
| Job | Price | With ROT |
|---|---|---|
| RCD 4-pole 25 A, 30 mA | SEK 961 | SEK 673 |
| RCD 4-pole 25 A, 30 mA, with small enclosure | SEK 1,286 | SEK 900 |
| RCBO 2-pole 10 A with small enclosure, for underfloor heating | SEK 1,350 | SEK 1,243 |
Materials, installation and VAT are included in the prices. A travel charge of SEK 500 is added. The price with ROT is the price after the Swedish ROT tax deduction for labour on your home (ROT-avdrag), if you are entitled to it, and the conditions for ROT can vary. The prices apply to a standard installation. Fault-finding in the existing installation is not included.
In an old fuse box with screw-in fuses (proppskåp) there is not always room for an RCD. It can then go in an enclosure of its own beside the box, or the whole unit is replaced with a new one with an RCD and circuit breakers. Sizes and prices are under consumer units in the price list.
When to get in touch
If you have an RCD that cuts the power when you test it, you do not need to do anything more than keep testing. Get in touch if the house has no RCD, if the test button does not cut the power or if the RCD dates from before 1996. If the consumer unit is going to be replaced anyway, it is simplest to sort out the RCD at the same time, and how such a replacement is done is described on the page about replacing the consumer unit.
Sources
- Elsäkerhetsverket – The RCD, your safety (in Swedish)
- Elsäkerhetsverket – When was the requirement for RCDs for sockets and final circuits introduced in the regulations? (in Swedish)
- Elsäkerhetsverket – Is there a requirement for RCDs to be installed in homes? (in Swedish)
- Elsäkerhetsverket – Do I have to install an RCD when the consumer unit is replaced? (in Swedish)
- Elsäkerhetsverket – How often should I test my RCD? (in Swedish)
- Elsäkerhetsverket – When do you have to have an RCD? (in Swedish)